Thermal Imaging Electrical Inspection in Winnipeg

thermal imaging electrical inspection

Most electrical failures in commercial and industrial buildings give a warning before they happen: heat. A thermal imaging electrical inspection uses an infrared camera to find that heat in panels, switchgear, motor control centres and disconnects while the equipment is running, long before a connection burns open or a breaker trips during production. For facility and maintenance managers in Winnipeg and across Manitoba, it is one of the most practical ways to find problems you cannot see with the covers on.

What Infrared Scans Find in Commercial and Industrial Gear

An infrared camera shows surface temperature differences. On electrical equipment, an unexpected hot spot almost always points to resistance, overload or imbalance. The scan does not tell you everything, but it tells you where to look first.

The most common findings include:

  • Loose or degraded connections: lugs, bus bolts and terminal screws that have loosened from vibration, thermal cycling or poor original torque. A loose connection adds resistance, and resistance makes heat that feeds on itself.
  • Overloaded circuits: conductors or breakers running hotter than their neighbours because the load has grown since the circuit was installed. This is common after tenant improvements, added production lines or new rooftop equipment.
  • Phase imbalance: one phase of a three phase feeder running noticeably hotter than the other two. Imbalance stresses motors, transformers and neutrals, and it often traces back to how single phase loads were distributed.
  • Failing components: fuse clips that have lost tension, breakers with internal wear, contactors with pitted contacts and overload relays that are heating abnormally.
  • Transformer and motor issues: uneven heating on transformer windings or connections, and hot motor terminal boxes that suggest a termination problem.

Comparison is what makes the scan useful. A trained technician looks at similar components under similar load and flags the one that stands out, rather than relying on a single temperature number.

Why Scanning Under Load Matters

Infrared only finds problems that are producing heat, and equipment only produces meaningful heat when it is carrying current. A panel scanned at night with the plant idle can look perfectly clean and still have a connection that glows at full production.

When planning the scan, think about:

  • Timing: schedule it during normal operating hours or a known peak, not during a shutdown or a slow shift.
  • Load records: note what was running. A finding on a lightly loaded circuit may be more serious than it looks, because the temperature will climb as load increases.
  • Access: covers usually have to come off for a clear line of sight, unless infrared windows or viewing ports are installed. Removing covers on energized equipment is energized work and must follow CSA Z462 practices, including risk assessment, approach boundaries and the right personal protective equipment.
  • Operations coordination: let production or building operations know which areas will be opened and when, so nobody is surprised by a crew in the electrical room.

Safety is not a side note here. Our approach to energized work and site safety is outlined on our workplace safety page, and it applies to every scan we perform.

What a Good Thermal Imaging Report Should Include

A thermal image on its own is not a deliverable. The value is in a report your maintenance team can act on and that you can compare against next year. Ask for a report that includes:

  • Equipment identification for every finding, matched to your panel schedules or asset tags
  • A thermal image and a matching visual photo, so the location is obvious to whoever does the repair
  • Measured temperatures and the comparison reference used, such as an adjacent phase or a similar component
  • Load conditions at the time of the scan
  • A priority ranking, so you know what needs attention immediately and what can wait for a planned outage
  • A recommended corrective action for each finding
  • A list of equipment that was scanned with no findings, so you know coverage was complete

If a report cannot tell your electrician exactly which lug on which breaker is the problem, it is not finished.

Follow-Up Repairs: Closing the Loop

The scan is the diagnosis. The repair is where the risk actually comes down. Most findings call for de-energizing the equipment, cleaning and re-terminating connections, replacing damaged components, or redistributing load.

Plan follow-up work with these points in mind:

  • Group repairs by outage: bundle findings in the same switchboard or MCC so you only shut down once.
  • Look past the hot spot: an overheated connection may have damaged insulation or the conductor itself. Repair what the heat affected, not just the bolt.
  • Find the cause: an overloaded circuit needs a load review, not just a new breaker. Imbalance needs loads redistributed.
  • Rescan after repair: a follow-up scan under load confirms the problem is actually gone.

Our industrial electrical services and commercial electrical team handle both the scan and the corrective work, so findings do not sit in a binder waiting for someone to schedule them.

Fitting Thermal Imaging Into Your Maintenance Program

A thermal imaging electrical inspection works best as part of a regular maintenance program rather than a one-time event. CSA Z463 provides guidance on maintaining electrical systems, and infrared scanning fits naturally alongside visual inspection, cleaning, torque checks and testing.

To get the most from it:

  • Scan on a regular schedule so you can trend results from one year to the next
  • Prioritize critical equipment: main switchgear, MCCs feeding production, distribution serving life safety systems and anything with a history of trouble
  • Add a scan after major changes, such as new equipment, service upgrades or tenant fit-outs
  • Keep reports together so trends and repeat locations are easy to spot

For Manitoba facilities, consider seasonal load as well. Heating loads in winter and cooling loads in summer change which circuits are working hardest.

Frequently Asked Questions

Does the building or plant need to shut down for the scan?

No. The scan is done with equipment energized and under load. Shutdowns are only needed later, to repair what the scan finds.

Can thermal imaging find every electrical problem?

No. It finds problems that produce heat. It will not find issues like insulation breakdown on idle circuits or settings errors on protective devices, which is why it is one part of a broader maintenance program.

Is a thermal imaging electrical inspection only for industrial plants?

No. Office buildings, retail, multi-tenant and institutional properties all have switchboards, panels and rooftop equipment feeds that benefit from regular scanning.

Book Infrared Scanning for Your Winnipeg Facility

Clean Energy Electrical Group performs infrared scanning on commercial and industrial electrical systems across Winnipeg and Manitoba, with licensed electricians, COR safety certification and a project lead who follows findings through to repair. We can scan during your operating hours, report clearly and schedule corrective work around your production or tenants.

To plan a scan or repair work, request a project quote or call us at 204-306-2121.